Closed Bug 1220920 Opened 10 years ago Closed 10 years ago

XO cross connect for SJC2

Categories

(Infrastructure & Operations Graveyard :: NetOps: DC Carrier, task)

task
Not set
normal

Tracking

(Not tracked)

RESOLVED FIXED

People

(Reporter: van, Assigned: van)

References

Details

tracking bug: FINAL A-side Demarc Point: SV1::01420:MOZILLA, 0107, PP:0107:138845, 23, 0 FINAL Z-side Demarc Point: SV1::01360:XO COMMUNICATIONS, 0000, CP:0000:74837, 9, 10 Carrier Circuit ID: SF/LZXX/150227/ /TQW / Media Type: Single-Mode Fiber Serial Number A-Side: 20059908 Serial Number Z-Side:
Assignee: network-operations → vle
cross connect patched but no light detected even after rolling fiber. emailed our XO rep to confirm they've configured their end. vle@border1.mgmt.sjc2.mozilla.net> show interfaces diagnostics optics xe-1/2/5| grep dBm Laser output power : 0.7190 mW / -1.43 dBm Receiver signal average optical power : 0.0005 mW / -33.01 dBm Laser output power high alarm threshold : 1.5840 mW / 2.00 dBm Laser output power low alarm threshold : 0.1580 mW / -8.01 dBm Laser output power high warning threshold : 1.2580 mW / 1.00 dBm Laser output power low warning threshold : 0.1990 mW / -7.01 dBm Laser rx power high alarm threshold : 1.7783 mW / 2.50 dBm Laser rx power low alarm threshold : 0.0100 mW / -20.00 dBm Laser rx power high warning threshold : 1.5849 mW / 2.00 dBm Laser rx power low warning threshold : 0.0158 mW / -18.01 dBm
equinix fixed the light issue. xe-1/2/5 up up xe-1/2/5.0 up up inet 216.156.84.30/30 multiservice
Status: NEW → RESOLVED
Closed: 10 years ago
Resolution: --- → FIXED
Blocks: 1224350
Product: Infrastructure & Operations → Infrastructure & Operations Graveyard